WMPLMRU120 Possible measurements: earth resistance measurment with 3-pole,4-pole method, earth resistance measurement without disconnecting measured earths (using clamp), continuity of equipotential b
详情介绍:
Possible measurements:
  • earth resistance measurment with 3-pole,4-pole method,
  • earth resistance measurement without disconnecting measured earths (using clamp),
  • continuity of equipotential bondings and protecting conductors
  • two clamps earth resistance measurement without auxiliary test probs,
  • earth resistivity measurement,

MRP-120 Technical Specifications
 
  • Testing AC residual current circuit breakers:
    -  measurement of tripping current IA 
    -  measurement of disconnection time t
    -  testing of standard and selective RCDs for the rated current values 10, 30, 100, 300 and 500 mA,
    - testing current waveform: sinusoidal, selection of initial phase (0° or 180°),
    - ability to measure touch voltage UB and earth resistance RE without tripping the circuit breaker,
    - select safe voltage value threshold at 25V and 50V and additionally at 12.5V for selective RCDs,
    - protection against exceeding the safe voltage setting during a measurement,
    - detection of L and N leads swap and its automatic correction performed internally by the meter.
  • AC voltmeter function in the range 0...250V.
  • Rapid check of PE lead connection using a touch electrode.
  • Backlit LCD.
  • Memory to store up to 400 cels of measurement results with an ability to transfer the data to a PC.
  • Battery status indicator.
  • AUTO-OFF function.
  • Meter meets the requirements of the standard EN 61557.

 

Rated operational conditions:
- operating temperature: 0...+40°C
- storage temperature: -20...+60°C
- reference temperature: +23 ± 2°C
- temperature coefficient:
    for touch voltage measurements: ± 1% of the measured value ± 1 digit /10°C
    for disconnection current measurement: ± 0,5% of the measured value /10°C
- rated mains voltage: 187...250V
- rated mains frequency: 50Hz ±0,5Hz

Electric security:
- type of insulation: double, according to  EN 61010-1 and IEC 61557
- measurement category: CAT III 300V acc. to EN 61010-1
- protection class acc. to EN 60529:    IP40

Other technical data:
- voltage range for RCD testing: 187...250V
- power supply: alkaline batteries LR6 (AA) (2 pcs.)
- dimensions: 230 x 67 x 35 mm
- weight: approx. 380 g
- time to auto-off: 2 minutes
- display: LCD 3 digits, 14mm high
- quality standard: ISO 9001

 


Earthing resistance measurement (RE):

Selected
rated RCD
current
Range Resolution

Measurement
current

Accuracy
10mA 0,01...5,00kΩ 0,01kΩ 4mA 0...+10% m.v. ± 5 digits
30mA 0,01...1,66kΩ 12mA 0...+10%  m.v. ± 3 digits
100mA 1...500Ω 40mA 0...+4% m.v. ± 4 digits
300mA 1...166Ω 120mA
500mA 1...100Ω 200mA 0...+4% m.v. ± 3 digits

RCD disconnection test and the response time measurement tA

RCD type Range Resolution Accuracy
 
Standard 0...200ms 1ms  ±(2%m.v. + 1 digits)
Selective 0...500ms

 
RCD disconnecting current measurement for a sine AC test current (IA)

Selected
rated RCD
current
Range Resolution

Measurement
current

Accuracy
10mA 3,3...10,0mA 0,1mA 0,3mA x IΔn
...1,0mA x IΔn
±5% IΔn
30mA 9,0...30,0mA
100mA 33...100mA 1mA
300mA 90...300mA
500mA 150...500mA

• start of the measurement can be selected either from the positive or negative half sine
   period of the test current
• test current flow time - max. 3200ms

IΔn - rated residual current value RCD

AC voltage measurement

Range Resolution Accuracy
0...250V 1V ±(1% m.v. + 2 digits)


Touch voltage measurement referred to the rated residual current (UB)
Test range: 10...50V
 

Selected
rated RCD
current
Range Resolution

Measurement
current

Accuracy
10mA 0...50V 0,1V 4mA 0...+10% m.v.
± 5 digits
30mA 12mA
100mA 40mA 0...+4% m.v.
± 5 digits
300mA 120mA
500mA 200mA
标题: