简单介绍:
Description: Temperature Limit Controller
Process Inputs: 0.4-2.0 V, 1-5 V, 0-10 V, -10 to 20 mV, 0-100 mV, 4-20 mA (4-20 mA requires resistor PDX-RES1)
Temperature Inputs: J, K, T, E, B, R, S, L, U,
详情介绍:
|
System Condition | Over Limit Timer | Max/Min Input Value |
EASY SETUP & PROGRAMMING
All programming of a Nova Digital Controller is done through the front panel. No switches or jumpersare required.
Front Panel Buttons
- Hold the RST button for 3 seconds when the unit is not in over limit conditions to reset the latching limit relay
- Press the SET/ENT button to confirm an entered value. Hold the button for 3 seconds to enter or exit the setup groups. Press the SET/ENT button to access the next parameter when in a setup group.
- Press the Up button to increase numerical values including the set point or scroll through parameter options and group menus.
- Press the Down button to decrease numerical values including the set point or scroll through parameter options and group menus.
- Press the LEFT button to move to the next digit during numerical value programming.
Setup Group Menus
For easy setup parameter navigation, all parameters are grouped by category. To access the group menus, press and hold the SET/ENT button for 3 seconds. Navigate through the group menus using the UP or DOWN buttons as shown. To enter a group menu to access setup parameters, press the SET/ENT button.Button |
PV Display |
Group Definition |
ENT | Password |
|
Control Group |
||
Input Group | ||
Alarm Group | ||
Retransmission Group | ||
Communications Group |
*This group menu appears only on models with the serial communications option.
Menu Password
To prevent unauthorized changes to key parameters, a user defined lockout password must be entered to access the group menus that are not commonly used during operation. Enter the password at the prompt when navigating the group menus by pressing the SET/ENT button. The default password is 0.Easy to Use Menu Structure
Each setup parameter is located in an associated menu group.
|
For a complete list of setup parameters, their functions, and setting options, refer to the PD570 Series Instruction Manual.
PROCESS & TEMPERATURE INPUTS
Nova Controllers use a single universal input that accepts process and temperature inputs.Thermocouple: J, K, T, E, R, B, S, L, N, U, W, Platinel II
RTD: Pt100 (0.00385), JPt100 (0.00392)
Process: | -10 to 20 mV, 0 to 100 mV 0.4 to 2 V, 1 to 5 V, 0 to 10 V 4 to 20 mA input with a resistor shunt |
OPERATION
Powerful Relay Functionality
All PD570 Series Limit Controllers have a 3 A Form C (SPDT) latching relay for use in limit control functions. All PD570 Series controllers also have a 1 A Form A (SPST) alarm relay.- High or Low PV Limit Latching Relay
- Forward and Reverse (Fail-Safe) Latching and Alarm Relays
- High/Low and Set Point Deviation Alarms
- Fail-Safe and Standby Alarms
- Relay Delays and Reset Deadband
Latching Relay Over Limit Control
When an over limit condition occurs, the latching relay will trigger. The relay must be reset manually and can only be reset once the input returns to normal operating conditions as established by the set point and programmable hysteresis.4-20 mA Retransmitting Output
A 4-20 mA powered output is standard on all PD570 Series models. The output can be programmed to transmit over any input scale for any input type or based on the set point value.Transmitter Loop Power Supply
The 4-20 mA retransmitting output may be configured to provide a 14 to 18 VDC @ 20 mA transmitter power supply.Input Bias Adjustment
Up to five bias points set to specific input values can be used to provide precise offset adjustments through 4 bias zones. The controller will use the offset to create a smooth input value curve leading up to the bias points.Max/Min Input Readings
Easily view the maximum or minimum input value reached during over limit conditions without entering the setup menus.Display Over Limit Time
A timer to track the over limit times in minutes and seconds or hours and minutes is easily displayed from the operating menu.Serial Communications & Adapters
Nova controllers with the serial communications option can be used for data acquisition or Modbus communication (RTU and ASCII). Nova controllers transmit via RS-485. The PDA7485 RS-232 to RS-485 and PDA8485 USB to RS-485 converters are available for use with the Nova Multi-Monitoring software or other PC applications.PDA8485 |
PDA7485 |
NOVA PC SOFTWARE
Any Nova Controller with the serial communication option can be configured to interface with the Nova Multi-Monitoring PC software. Up to 30 controllers can be monitored and operated, and each can use independent data logging.- Easy to Set Up and Use
- Connect up to 30 Nova meters
- View PV and Alarm Status
- Log, View, and Save Data in Spreadsheet Files
Specifications
System Requirements: Windows® 95\98\ME\2000\XPCommunications: An RS-232 to RS-485 or USB to RS-485 converter may be used for communication with a PC and Nova Multi-Monitoring Software.
Number of Units: Up to 30 Nova Controllers
Baud Rate: 9,600 to 19,200 bps
Data Logging: Graph and save data as .hdr format. Each controller saves graphs independently. Data exportable in spreadsheet format.
Logging Interval: 1 second to 24 hours
Simultaneous Monitoring
Simultaneously monitor up to 30 Nova Controllers and view the PV, SP, and alarm status for all connected controllers. The main view screen also displays the basic model numbers of all connected units. Any series of Nova Controllers with the serial communication option may be monitored with this software.Simultaneously View Up to 30 Nova Controllers
Remote Set Point Control and Indication
A detailed operation screen for each controller indicates the model number of the controller, the PV, SP, alarm conditions, high or low PV input, and the over limit condition timer. The set point, direction of operation (high or low limit control) and startup relay condition can all be set through this screen.Data Acquisition
PV and SP data can be logged independently for each unit, and each can have a distinct file name, save location, and logging interval. This data can be graphed using the Data Viewer for quick and clear analysis. Logged data can be exported into spreadsheet format.View Logged Data Graphs and Export Data
CONNECTIONS
PD570
PD578
MODEL NUMBER GUIDE
The following guide describes the possible PD570 Series Nova Process & Temperature Limit Controller model numbers.Refer to the price list for the complete list of models and accessories.
DIMENSIONS AND PANEL CUTOUTS
PD570
1/16 DIN (48 x48)
PD578
1/4 DIN (96 x 96)
SPECIFICATIONS
Except where noted all specifications apply to operation at +25°C.General
Display: Dual 4 digits, red LED, -1999 to 9999DIN SIZE | PV Display Inch (mm) |
SP Display Inch (mm) |
Weight oz (g) |
1/16 | 0.45 (11.3) | 0.37 (9.5) | 7.0 (198) |
1/4 | 0.81 (20.5) | 0.43 (11.0) | 13.9 (394) |
1/16 DIN: IP65
1/4 DIN: IP55
Programming Methods: Four front panel buttons and Modbus
Noise Filter: Programmable 1 to 120 seconds, or off
Display Update Rate: 4/second
Max/Min Display: Stored until reset by user or meter is turned off.
Password: Restricts modification of programmed settings.
Non-Volatile Memory: Settings stored for a minimum of 10 years
Power: 100-240 VAC, 50/60 Hz, 10 W
Required Fuse: UL Recognized, 1 A, 250 V, slow-blow
Isolation: 2300 V input/output-to-power line; 4 kV relay output-to-input/output/power line.
Operating Temperature: 10 to 50°C
Storage Temperature: -40 to 85°C
Relative Humidity: 20 to 90% non-condensing
Enclosure: 1/8 & 1/4 DIN available; impact-resistant plastic; color: black
UL File Number: E244207; Process Control Equipment
Approvals: UL & C-UL Recognized, CE Compliant
Warranty: 3 years parts & labor
Extended Warranty: 1 or 2 years, refer to Price List for details.
Temperature Inputs
Inputs: Factory calibrated, field selectable: J, K, T, E, B, R, S, L, U, N, W, and Platinel II thermocouples and 100 Ω platinum RTD (0.00385 or 0.00392 curve)Cold Junction Reference: Automatic or off
Offset Adjustment: Four programmable input bias zones
Sensor Break: Up or down scale, user selectable; display reads S.OPN; alarm relays will follow the up or down scale selection.
Type | Range (°C) | Range (°F) | Accuracy | |
K1 | -200 to 1370 | -300 to 2500 | >0ºC: ±0.1% FS ±1 count <0ºC: ±0.2% FS ±1 count |
|
K2 | -199.9 to 999.9 | 0 to 2300 | ||
J | -199.9 to 999.9 | -300 to 2300 | ||
T | -199.9 to 400.0 | -300 to 750 | ||
E | -199.9 to 999.9 | -300 to 1800 | ||
B | 0 to 1800 | 32 to 3300 | >400ºC: ±0.15% FS ±1 count <400ºC: ±5% FS ±1 count |
|
R | 0 to 1700 | 32 to 3100 | ±0.15% FS ±1 count | |
S | 0 to 1700 | 32 to 3100 | ||
L | -199.9 to 900.0 | -300 to 1600 | >0ºC: ±0.1% FS ±1 count <0ºC: ±0.2% FS ±1 count |
|
U | -199.9 to 400.0 | -300 to 750 | ||
N | -200 to 1300 | -300 to 2400 | >0ºC: ±0.1% FS ±1 count <0ºC: ±0.25% FS ±1 count |
|
W | 0 to 2300 | 32 to 4200 | ±0.2% FS ±1 count | |
Platinel II | 0 to 1390 | 32 to 2500 | ±0.1% FS ±1 count | |
PtA | -199.9 to 850.0 | -300 to 1560 | ±0.1% FS ±1 count | |
PtB | -199.9 to 500.0 | -199.9 to 999.9 | ||
PtC | -19.99 to 99.99 | -4.0 to 212.0 | ±0.2% FS ±1 count | |
JPtA | -199.9 to 500.0 | -199.9 to 999.9 | ±0.1% FS ±1 count | |
JPtB | -150.0 to 150.0 | -199.9 to 300 |
Process Inputs
Inputs: Field selectable: 0.4 to 2.0 V, 1 to 5 V, 0 to 10 V, -10 to 20 mV, 0 to 100 mV. 4-20 mA input requires 100Ω resistor connected across input terminals (order P/N: PDX-RES1).Accuracy: ±0.1% FS ±1 count
Decimal Point: Up to 3 decimals: 9.999, 99.99, 999.9, or 9999
Calibration: All inputs are calibrated at the factory
Scale Range: User programmable over entire range
Transmitter Supply: 14 to 18 VDC @ 20 mA; available instead of retransmitting analog output; selection is made through the front panel.
Limit Control Relay and Indicators
Ratings: Latching, 1 Form C (SPDT); rated 3 A @ 30 VDC or 3 A @ 250 VAC resistive loadRelay Operation: User may select high or low limit operation, forward or reverse (fail-safe) mode.
Reverse Operation (Fail-Safe): Programmable; relay coil is energized in non-alarm condition. In case of power failure, relay will go to alarm state.
Forward Operation: Relay coil is energized in alarm condition. In case of power failure, relay will go to non-alarm state.
Hysteresis: 0-10% FS, user selectable; manual reset allowed after condition has been corrected.
Out LED: Relay status indicator. LED is on when relay is de-energized (during over limit conditions in reverse operation).
Over Limit LED: Over LED is on when system is in over limit condition. LED will go off once system returns to normal condition.
Over Limit Timer Display: Time stored since last occurrence of over limit condition or until controller is turned off.
Alarm Relays
Ratings: 1 Form A (SPST); rated 1 A @ 30 VDC or 1 A @ 250 VAC resistive loadHigh/Low Alarm: User may program alarm for absolute value, high or low operation, forward or reverse (fail-safe) mode.
Deviation Alarm: User may program relay for high, low, or high/low range deviation alarm, forward or reverse (fail-safe) mode.
Alarm Deadband: 0-100% FS, user selectable
Alarm Delay: 0 to 99 minutes and 59 seconds
Reverse Operation (Fail-Safe): Programmable; relay coil is energized in non-alarm condition. In case of power failure, relay will go to alarm state.
Forward Operation: Relay coil is energized in alarm condition. In case of power failure, relay will go to non-alarm state.
Auto Alarm Initialization: Normal and standby operation. Normal alarm will reflect the state of the input to the controller at all times. Standby alarm will not trigger if the change to alarm state is a result of power up cycle, set point change, or alarm configuration change.
4-20 mA Retransmitting Output
Scaling Range: 4-20 mA output can be scaled for any displayAccuracy: ±0.1% FS
Power: Internally powered 4-20 mA output
Isolation: 500 V input-to-output
Output Loop Resistance: 600 Ω max
Serial Communications
Compatibility: EIA-485Protocol: PC, Modbus (ASCII, RTU)
Address: 1 to 99 (Max 31 units connected)
Baud Rate: 600 to 19,200 bps
Data: 7 or 8 bit, automatic when using Modbus protocol
Transmit Time Delay: 0 to 100 ms
Stop Bit: 1 or 2
Parity: None, even, or odd
ORDERING INFORMATIONProducts |
|||||
Model | Description | ||||
PD570-6RA-10 | Temperature Limit Controller; 2 Relays, 1 Analog; 1/16 DIN | ||||
PD570-6RA-14 | Temperature Limit Controller; 2 Relays, 1 Analog, RS-485; 1/16 DIN | ||||
Accessories |
|||||
Model | Description | ||||
PDA7485-I | RS-232 to RS-422/485 Isolated Converter | ||||
PDA7485-N | RS-232 to RS-422/485 Non-Isolated Converter | ||||
PDA8485-I | USB to RS-422/485 Isolated Converter | ||||
PDA8485-N | USB to RS-422/485 Non-Isolated Converter | ||||
PDX-RES1 | 100 Ω Precision Resistor for NOVA 4-20 mA Input |