简单介绍:
Description: Digital Temperature Meters
Process Inputs: 0.4-2.0 V, 1-5 V, 0-10 V, -10 to 20 mV, 0-100 mV, 4-20 mA (4-20 mA requires resistor PDX-RES1)
Temperature Inputs: J, K, T, E, B, R, S, L, U, N,
详情介绍:
EASY SETUP & PROGRAMMING
All programming of a Nova Digital Meter is done through the front panel. No switches or jumpers are required.Front Panel Buttons
- Press the SET/ENT button to confirm an entered value. Hold the button for 3 seconds to enter or exit the setup
groups. Press the SET/ENT button to access the next parameter when in a setup group.
- Press the Up button to increase numerical values or scroll through parameter options and group menus.
- Press the Down button to decrease numerical values or scroll through parameter options and group menus.
- Press the LEFT button to move to the next digit during numerical value programming.
Setup Group Menus
For easy parameter navigation, all parameters are grouped by category. To access the group menus, press and hold the SET/ENT button for 3 seconds. Navigate through the group menus using the UP and DOWN arrow buttons as shown. To enter a group menu to edit or view parameters, press the SET/ENT button.Button |
PV Display |
Group Definition |
ENT | Password |
|
Control Group |
||
Input Group | ||
Alarm Group | ||
Retransmission Group | ||
Communications Group * |
*This group menu appears only on models with the serial communication option.
Menu Password
To prevent unauthorized changes to key parameters, a user defined lockout password must be entered to access the group menus that are not commonly used during operation. Enter the password at the prompt when navigating the group menus by pressing the SET/ENT button. The default password is 0.Easy to Use Menu Structure
Each parameter is located in an associated menu group.
|
For complete list of setup parameters, their functions, and setting options, refer to the PD560 Series Instruction Manual.
PROCESS & TEMPERATURE INPUTS
Nova Digital Meters use a single universal input that accepts process and temperature inputs.Thermocouple: J, K, T, E, R, B, S, L, N, U, W, Platinel II
RTD: Pt100 (0.00385), JPt100 (0.00392)
Process: | -10 to 20 mV, 0 to 100 mV 0.4 to 2 V, 1 to 5 V, 0 to 10 V 4 to 20 mA input with a resistor shunt |
OPERATION
Alarm Relays
All PD560 Series Digital Meters have a standard 3 A Form C (SPDT) alarm relay. Up to two additional 1 A Form A (SPST) relays may be added. All relays can be programmed for a variety of alarm types.
- High/Low Alarms
- Set Point Deviation Alarms
- Fail-Safe and Standby Alarms
- Relay Delays and Reset Deadband
4-20 mA Retransmitting Output
A 4-20 mA powered output is standard on all PD560 Series models. The output can be programmed to transmit over any input scale for any input type.Transmitter Loop Power Supply
The 4-20 mA retransmitting output may be configured to provide a 14 to 18 VDC @ 20 mA transmitter power supply.Input Bias Adjustment
Up to five bias points can be used to provide precise offset adjustments at specific input values. The controller will use the offset to create a smooth input value curve leading up to the bias points.Display Max/Min Input Values
PD560 Digital Meters can record and display maximum and minimum input values. These values will be stored until reset by the user power to the meter is lost. Through the use of the user defined displays, these values can be accessible with the push of the SET/ENT button.Digital Input Max/Min Reset
Two digital inputs can be added as an optional feature. Digital inputs are activated by closing contacts or low logic levels. The configuration of the two inputs can be used to hold or reset the maximum and minimum input values simultaneously or independently.DISL | DI1 | DI2 | Operation |
1 | off | - | Reset MIN, MAX |
on | - | Start MIN, MAX | |
2 | off | - | Reset MIN |
on | - | Start MIN | |
- | off | Reset MAX | |
- | on | Start MAX |
Serial Communications & Adapters
Nova meters with the serial communications option can be used for data acquisition or with Modbus communication (RTU and ASCII). Nova meters transmit via RS-485. PDA7485 RS-232 to RS-485 isolated and non-isolated converters and PDA8485 USB to RS-485 isolated and non-isolated converters are available for use with the Nova Multi-Monitoring software or other PC applications.PDA8485 |
PDA7485 |
NOVA PC SOFTWARE
Any Nova Controller with the serial communications option can be configured to interface with the Nova Multi-Monitoring PC software. Up to 30 meters can be monitored and operated, and each can use independent data logging.- Easy to Set Up and Use
- Connect up to 30 Nova meters
- View PV and Alarm Status
- Log, View, and Save Data in Spreadsheet Files
Specifications
System Requirements: Windows® 95\98\ME\2000\XPCommunications: An RS-232 to RS-485 or USB to RS-485 converter may be used for communication with a PC and Nova Multi-Monitoring Software.
Number of Units: Up to 30 Nova Controllers
Baud Rate: 9,600 to 19,200 bps
Data Logging: Graph and save data as .hdr format. Each
controller saves graphs independently. Data exportable in spreadsheet format.
Logging Interval: 1 second to 24 hours
Simultaneous Monitoring
Simultaneously monitor up to 30 Nova Meters and view the PV and alarm status for all connected controllers. The main view screen also displays the basic model numbers of all connected units. Any series of Nova Controllers with the serial communications option may be monitored with this software.Simultaneously View Up to 30 Nova Controllers
Real Time Indication and Graphing
A detailed operation screen for each controller indicates the model number of the meter, PV, alarm conditions, and maximum and minimum input values. A live updating graph shows PV information as it is logged.Data Acquisition
PV data can be logged independently for each meter, and each can have a distinct file name, save location, and logging interval. This data can be graphed using the Data Viewer for quick and clear analysis. Logged data can be exported into spreadsheet format.View Logged Data Graphs and Export Data
CONNECTIONS
PD562
PD568
NO switches (external excitation not required) or open collector transistor
MODEL NUMBER GUIDE
The following guide describes the possible PD560 Series Nova Digital Process & Temperature Meter model numbers.Refer to the price list for the complete list of models and accessories.
DIMENSIONS AND PANEL CUTOUTS
PD562
1/8 DIN (H) (96 x 48)
PD568
1/4 DIN (96 x 96)
SPECIFICATIONS
Except where noted all specifications apply to operation at +25°C.General
Display: Dual 4 digits, red LED, -1999 to 9999DIN SIZE | PV Display Inch (mm) |
SP Display Inch (mm) |
Weight oz (g) |
1/8 (H) | 0.78 (19.8) | 0.45 (11.5) | 10.0 (285) |
1/4 | 0.81 (20.5) | 0.43 (11.0) | 13.9 (394) |
1/8 DIN: IP65
1/4 DIN: IP55
Programming Methods: Four front panel buttons and Modbus
Noise Filter: Programmable 1 to 120 seconds, or off
Display Update Rate: 4/second
Max/Min Display: Stored until reset by user or meter is turned off.
Password: Restricts modification of programmed settings.
Non-Volatile Memory: Settings stored for a minimum of 10 years
Power: 100-240 VAC, 50/60 Hz, 10 W
Required Fuse: UL Recognized, 1 A, 250 V, slow-blow
Isolation: 2300 V input/output-to-power line; 4 kV relay output-to-input/output/power line.
Operating Temperature: 10 to 50°C
Storage Temperature: -40 to 85°C
Relative Humidity: 20 to 90% non-condensing
Enclosure: 1/8 & 1/4 DIN available; impact-resistant plastic; color: black
UL File Number: E244207; Process Control Equipment
Approvals: UL & C-UL Recognized, CE Compliant
Warranty: 3 years parts & labor
Extended Warranty: 1 or 2 years, refer to Price List for details.
Temperature Inputs
Inputs: Factory calibrated, field selectable: J, K, T, E, B, R, S, L, U, N, W, and Platinel II thermocouples and 100 Ω (0.00385 or 0.00392 curve)Cold Junction Reference: Automatic or off
Offset Adjustment: Four programmable input bias zones
Sensor Break: Up or down scale, user selectable; display reads S.OPN; alarm relays will follow the up or down scale selection.
Type | Range (°C) | Range (°F) | Accuracy | |
K1 | -200 to 1370 | -300 to 2500 | >0ºC: ±0.1% FS ±1 count <0ºC: ±0.2% FS ±1 count |
|
K2 | -199.9 to 999.9 | 0 to 2300 | ||
J | -199.9 to 999.9 | -300 to 2300 | ||
T | -199.9 to 400.0 | -300 to 750 | ||
E | -199.9 to 999.9 | -300 to 1800 | ||
B | 0 to 1800 | 32 to 3300 | >400ºC: ±0.15% FS ±1 count <400ºC: ±5% FS ±1 count |
|
R | 0 to 1700 | 32 to 3100 | ±0.15% FS ±1 count | |
S | 0 to 1700 | 32 to 3100 | ||
L | -199.9 to 900.0 | -300 to 1600 | >0ºC: ±0.1% FS ±1 count <0ºC: ±0.2% FS ±1 count |
|
U | -199.9 to 400.0 | -300 to 750 | ||
N | -200 to 1300 | -300 to 2400 | >0ºC: ±0.1% FS ±1 count <0ºC: ±0.25% FS ±1 count |
|
W | 0 to 2300 | 32 to 4200 | ±0.2% FS ±1 count | |
Platinel II | 0 to 1390 | 32 to 2500 | ±0.1% FS ±1 count | |
PtA | -199.9 to 850.0 | -300 to 1560 | ±0.1% FS ±1 count | |
PtB | -199.9 to 500.0 | -199.9 to 999.9 | ||
PtC | -19.99 to 99.99 | -4.0 to 212.0 | ±0.2% FS ±1 count | |
JPtA | -199.9 to 500.0 | -199.9 to 999.9 | ±0.1% FS ±1 count | |
JPtB | -150.0 to 150.0 | -199.9 to 300 |
*Performance within recommended operating conditions (10 to 50 ºC, 20 to 90% RH)
Process InputsInputs: Field selectable: 0.4 to 2.0 V, 1 to 5 V, 0 to 10 V, -10 to 20 mV, 0 to 100 mV. 4-20 mA input requires 100 Ω resistor connected across input terminals (order P/N: PDX-RES1).
Accuracy: ±0.1% FS ±1 count
Decimal Point: Up to 3 decimals: 9.999, 99.99, 999.9, or 9999
Calibration: All inputs are calibrated at the factory
Scale Range: User programmable over entire range
Transmitter Supply: 14 to 18 VDC @ 20 mA; available instead of retransmitting analog output; selection is made through the front panel.
Alarm Relays
Ratings: 1 Form C (SPDT) standard; rated 3 A @ 30 VDC or 3 A @ 250 VAC resistive load. 1 or 2 Form A (SPST) optional; rated 1 A @ 30 VDC or 1 A @ 250 VAC resistive load
High/Low Alarm: User may program any alarm for absolute high or low operation, forward or reverse (fail-safe) mode.
Alarm Deadband: 0-100% FS, user select
Alarm Delay: 0 to 99 minutes and 59 seconds
Reverse Operation (Fail-Safe): Programmable, independent for each alarm. Relay coils are energized in non-alarm condition. In case of power failure, relays will go to alarm state.
Forward Operation: Relay coils are energized in alarm condition. In case of power failure, relays will go to non-alarm state.
Auto Alarm Initialization: Normal and standby operation independent for each alarm. Normal alarms will reflect the state of the input to the meter at all times. Standby alarms will not trigger if the change to alarm state is a result of power up cycle, set point change, or alarm configuration change.
4-20 mA Retransmitting Output
Scaling Range: 4-20 mA output can be scaled for any display
Accuracy: ±0.1% FS
Power: Internally powered 4-20 mA output
Isolation: 500 V input-to-output
Output Loop Resistance: 600 Ω max
Digital Inputs
Configuration: Two contacts. Two operating modes
Contacts: Normally open switches (external excitation note required) or open collector transistor
Open Circuit Voltage: Approximately 5 VDC
Logic Levels: LO = 0 to 0.8 VDC, HI = 4.7 to 28 VDC
Operation Modes: Mode 1: Store and reset max & min display values simultaneously. Mode 2: Store and reset max & min display values independently.
Serial Communications
Compatibility: EIA-485
Protocol: PC, Modbus (ASCII, RTU)
Address: 1 to 99 (Max 31 units connected)
Baud Rate: 600 to 19,200 bps
Data: 7 or 8 bit, automatic when using Modbus protocol
Transmit Time Delay: 0 to 100 ms
Stop Bit: 1 or 2
Parity: None, even, or odd
ORDERING INFORMATIONProducts |
|||||
Model | Description | ||||
PD562-6RA-00 | Temperature Meter; 1 Relay, 1 Analog Output | ||||
PD562-6RA-21 | Temperature Meter; 3 Relays, 1 Analog Output, 2 Digital Inputs | ||||
PD562-6RA-24 | Temperature Meter; 3 Relays, 1 Analog Output, RS-485 | ||||
PD568-6RA-00 | Temperature Meter; 1 Relay, 1 Analog Output; 1/4 DIN | ||||
PD568-6RA-21 | Temperature Meter; 3 Relays, 1 Analog Output , 2 Digital Outputs; 1/4 DIN | ||||
PD568-6RA-24 | Temperature Meter; 3 Relays, 1 Analog Output, RS-485; 1/4 DIN | ||||
Enclosures |
|||||
Model | Description | ||||
PDA2302 | Economical Plastic NEMA 4X Enclosure for 2 Type A, B, C, or E Meters | ||||
PDA2303 | Economical Plastic NEMA 4X Enclosure for 3 Type A, B, C, or E Meters | ||||
PDA2304 | Economical Plastic NEMA 4X Enclosure for 4 Type A, B, C, or E Meters | ||||
PDA2305 | Economical Plastic NEMA 4X Enclosure for 5 Type A, B, C, or E Meters | ||||
PDA2306 | Economical Plastic NEMA 4X Enclosure for 6 Type A, B, C, or E Meters | ||||
PDA2307 | Economical Plastic NEMA 4X Enclosure for 7 Type A, B, C, or E Meters | ||||
PDA2308 | Economical Plastic NEMA 4X Enclosure for 8 Type A, B, C, or E Meters | ||||
PDA2309 | Economical Plastic NEMA 4X Enclosure for 9 Type A, B, C, or E Meters | ||||
PDA2310 | Economical Plastic NEMA 4X Enclosure for 10 Type A, B, C, or E Meters | ||||
PDA2312 | Economical Plastic NEMA 4X Enclosure for 2 Type A, B, C, or E Meters | ||||
PDA2322 | Economical Plastic NEMA 4X Enclosure for 1 Type D + 1 Type C Meter | ||||
PDA2407 | Plastic NEMA 4X Enclosure for 1 Meter (Any Type) | ||||
PDA2408 | Plastic NEMA 4X Enclosure for 2 Type B Meters | ||||
PDA2409 | Plastic NEMA 4X Enclosure for 3 Type B Meters | ||||
PDA2410 | Plastic NEMA 4X Enclosure for 4 Type B Meters | ||||
PDA2411 | Plastic NEMA 4X Enclosure for 2 Meter (Any Type) | ||||
PDA2414 | Plastic NEMA 4X Enclosure for 1 Type D + 1 Type A, B, C or E Meter | ||||
PDA2504 | Plastic NEMA 4X Enclosure for 4 Type A, B, C, or E Meters | ||||
PDA2505 | Plastic NEMA 4X Enclosure for 5 Type A, B, C, or E Meters | ||||
PDA2506 | Plastic NEMA 4X Enclosure for 6 Type A, B, C, or E Meters | ||||
PDA2507 | Plastic NEMA 4X Enclosure for 7 Type A, B, C, or E Meters | ||||
PDA2508 | Plastic NEMA 4X Enclosure for 8 Type A, B, C, or E Meters | ||||
PDA2509 | Plastic NEMA 4X Enclosure for 9 Type A, B, C, or E Meters | ||||
PDA2510 | Plastic NEMA 4X Enclosure for 10 Type A, B, C, or E Meters | ||||
PDA2512 | Plastic NEMA 4X Enclosure for 2 Type A, B, C, or E Meters | ||||
PDA2522 | Plastic NEMA 4X Enclosure for 1 Type D + 1 Type C Meter | ||||
PDA2604 | Stainless Steel NEMA 4X Enclosure for 4 Type A,B, C or E Meters | ||||
PDA2605 | Stainless Steel NEMA 4X Enclosure for 5 Type A,B, C or E Meters | ||||
PDA2606 | Stainless Steel NEMA 4X Enclosure for 6 Type A,B, C or E Meters | ||||
PDA2622 | Stainless Steel NEMA 4X Enclosure for 1 Type D + 1 Type C Meter | ||||
PDA2704 | Steel NEMA 4 Enclosure for 4 Type A, B, C, or E Meters | ||||
PDA2705 | Steel NEMA 4 Enclosure for 4 Type A, B, C or E Meters | ||||
PDA2706 | Steel NEMA 4 Enclosure for 5 Type A, B, C or E Meters | ||||
PDA2722 | Steel NEMA 4X Enclosure for 1 Type D + 1 Type C Meter | ||||
PDA2811 | Low-Cost Plastic NEMA 4X Enclosure for 1 Meter (Type A, B, C or E) | ||||
PDA2812 | Low-Cost Plastic NEMA 4X Enclosure for 2 Meters (Any type) | ||||
PDA2821 | Low-Cost Plastic NEMA 4X Enclosure for 1 Type D Meter + 1 Type A, B, C or E Meter | ||||
Accessories |
|||||
Model | Description | ||||
PDA7485-I | RS-232 to RS-422/485 Isolated Converter | ||||
PDA7485-I | RS-232 to RS-422/485 Isolated Converter | ||||
PDA7485-N | RS-232 to RS-422/485 Non-Isolated Converter | ||||
PDA7485-N | RS-232 to RS-422/485 Non-Isolated Converter | ||||
PDA8485-I | USB to RS-422/485 Isolated Converter | ||||
PDA8485-I | USB to RS-422/485 Isolated Converter | ||||
PDA8485-N | USB to RS-422/485 Non-Isolated Converter | ||||
PDA8485-N | USB to RS-422/485 Non-Isolated Converter | ||||
PDX-RES1 | 100 Ω Precision Resistor for NOVA 4-20 mA Input | ||||
PDX-RES1 | 100 Ω Precision Resistor for NOVA 4-20 mA Input |