The PD7000 boasts specifications and functionality that clearly makes it one of the most advanced temperature meters available. Its dual-line 6-character display, function keys, and optional expansion
详情介绍:

ProVu logo
 


PD7000 ProVu Dual Line 6 digit Temperature meter 

  • J, K, T, E, R, S, B, N, C Thermocouples
  • 100 or 1000 Ω Platinum, 10 Ω Copper, 120 Ω Nickel RTDs
  • 1° or 0.1° Resolution
  • Averages up to 10 RTD Sensors
  • Automatic Cold Junction Compensation
  • NEMA 4X, IP65 Front
  • Universal 85-265 VAC or 12/24 VDC Input Power
  • Large Dual-Line 6-Character Display, 0.60" & 0.46"
  • Programmable Displays & Function Keys
  • Sunlight Readable Display models
  • 2 or 4 Relays + Isolated 4-20 mA Output Options
  • External 4-Relay & Digital I/O Expansion Modules
  • RS-232, RS-422/485 Serial Communication Options
  • Modbus® RTU Protocol Standard

ProVu PD7000 Diagram
 

INTRODUCTION

The ProVu meter boasts specifications and functionality that clearly makes it one of the most advanced temperature meters available. Its dual-line 6-character display, function keys, and optional expansion modules are only a few of the special features available on the ProVu.


 

Versatile

The PD7000 accepts many more thermocouple types and RTDs than earlier models. It can be configured to have either a 1° or 0.1° display resolution on any type of sensor input. The lower display makes configuration simpler. The display itself is quite configurable. There are many relay functions for up to 8 relays; including an Interlock Relay function. The 4-20 mA output can represent up to 12 different parameters/variables. This makes the PD7000 one of the most versatile meters on the market.


 

FRONT PANEL DISPLAY

Precise, Accurate, and More Informative

ProVu's large 0.6" upper display provides an accurate and precise 4 or 5-digit view of the temperature measurement.


 

Configurable

The upper display can be programmed to indicate current temperature, maximum or minimum temperature, alternating maximum/minimum temperatures, one of eight alarm set points, or Modbus input. The lower display can also be configured to display engineering units, set points, user defined legends, or simply turned off.
PD7000 ProVu Dual Line 6 digit process meter Function Keys

 

Function Keys

There are three function keys available to the user. These keys can be programmed to trigger certain events
( i.e. acknowledge alarms, reset max and/or min, disable/enable output relays, or hold current relay states), provide direct menu access points, and more.

Learn more about using the ProVu's Function Keys by watching a video click here to watch.


 

Optional SunBright Display Models

ProVu's SunBright display models have an extraordinarily bright LED display. They are perfect for applications where the meter is in direct sunlight or in applications where visibility may be impaired by smoke, fog, dust, or distance. There are 8 user selectable intensity levels to choose from on all ProVu models. This option is available on all ProVu models.


 

Easy to Use

The user friendly dual-line display makes the ProVu easy to set up & program. Input selection and configuration is conveniently set up via rear switches and front panel programming. Three levels of password protection help maintain the reliability of the programming.Input and display setup for the ProVu PD7000

Three Tier Password Protection

The ProVu offers 3 levels of password protection:

  • Level 1 protection allows the operator use of only the 3 pre-configured function keys on the front panel without a password.
  • Level 2 protection allows the operator use of only the function keys and the ability to change set points without a password.
  • Level 3 protection restricts the operator from using the function keys and all meter configuration menus without a password.
PD7000 Dual Line 6 digit process meter Front Panel Display Rugged

Rugged

A unique front panel design makes the ProVu nearly impenetrable in typical applications. Here, the ProVu easily survives a direct hit on the display from a heavy 2" solid stainless steel ball dropped from eight feet.


 

Simplified & Dynamic Menu System

The ProVu minimizes the menu selections by auto-detecting the installed options to determine what menu navigation is required. For example, extra menu items for the relay expansion module, I/O expansion, etc. are not present unless those options have been installed. This is an example of keeping the product simply sophisticated.


 

Max/Min Display

Max/Min (or Peak/Valley) is standard on the ProVu PD7000. Either display can be configured to show either maximum or minimum excursion since last reset. The displays can also be configured to toggle between Max and Min values. Both values can be simply reset from the front panel.


 

Environmentally Protected

The ProVu has standard UV protection, a NEMA 4X front panel, extremely durable face plate, performs in wide ambient operating temperatures, and is CE Certified (high noise and RF immunity).


 

DIGITAL COMMUNICATIONS

Modbus® RTU Serial Communications

After the purchase of a serial communication adapter for the ProVu meter, any Modbus-ready Master device can communicate with the meter using the ever-popular Modbus communications protocol included in every ProVu. This greatly increases the flexibility of the meter. Modbus provides much more capability than read PV and write set points. Below are some examples of other things that can be done with ProVu's Modbus communications.

  • Send a 6-character message to the lower display upon an event
  • Convert a digital value to a 4-20 mA signal
  • Remote user control (i.e. change set points, acknowledge alarms)
  • Input a Modbus digital PV (in place of analog input)
  • Remote override of any, or all, relays and analog outputs

Modbus PV input and remote message
 

Meter Copy

The Copy feature is used to copy (or clone) all the settings from one ProVu to other ProVu meters in about 20 seconds! The Copy function is a standard feature on all meters. It does not require a communications adapter, only an optional cable assembly, P/N PDA1200. See the ordering information for complete details.
 

PD7000 dual-line 6 digit process meter Meter Copy




 

MULTIPLE SENSOR AVERAGING

The PD7000 can find the average temperature of up to 10 RTD probes connected in parallel. This new calculated value would then be treated as the PV (temperature) displayed on the meter. The average temperature is also available via Modbus communications and as the retransmitted value for the optional 4-20 mA output.


 

METERVIEW® PRO SOFTWARE

View the ProVu Video
Click here to see the
ProVu videos

ProVu series meter using the PC-based MeterView Pro (MVP) software (serial communications adapter required). MVP makes complete meter configuration simple and fast. Copying one meter configuration to another, as well as saving or retrieving a meter configuration file is a snap. MVP's linearization utility makes even a 32-point linearization task clear and easy to do. We also included a basic meter monitor and data logger for use with a ProVu. Of course, with ProVu's powerful Modbus protocol, custom programs can be made even more versatile. For more details on MeterView Pro, click here.



Monitoring and Datalog

Monitor and Datalog

Setup

Setup

Relays

Relays




 

ProVu VIDEOS

Watch a quick demonstration on how the ProVu works and also how the function keys can simplify functionality. These and other videos are available at here.


PD7000 Provu dual-line 6 digit process meter Field Expandable options

FIELD EXPANSION MODULES

Add functionality to the ProVu in the field with easy-to-install external expansion modules. Add RS-232 or RS-422/485 communications, I/O modules (up to 2), and 4-relay expansion module. The menu items for these modules do not appear until the module is connected, simplifying the basic menu. Relay and digital I/O modules are shown below with optional DIN rail mounting kit, P/N PDA1002.


 

PDA1044 I/O Expansion Module

Four digital inputs and four digital outputs are available per expansion module. The ProVu meter will accept two of these modules. External digital inputs can function similarly to the front panel function keys. They can be configured to trigger certain events (i.e. acknowledge/reset alarms, reset max and/or min values, disable/enable all output relays, and hold current relay states), provide direct menu access point, or mimic front panel keys. The I/O module can be used to configure the ProVu remotely, in essence giving the user control of the four front panel push buttons. This feature is particularly useful if the meter is mounted inside an explosion-proof enclosure.

Digital outputs can be used to remotely monitor ProVu's alarm relay output states, or the states of a variety of actions and functions executed by the meter.


Relay Expansion Modules
 

PDA1004 Relay Expansion Module

An external module containing four 3 A Form A (SPST) relays can be added to the ProVu at anytime. Removable screw terminal blocks accept 12 to 22 AWG wire.


PDA1232 and PDA1485
 

PDA1232 & PDA1485 Communication Modules

Serial communications on the ProVu can be added anytime with external PDA1232 (RS-232) or PDA1485 (RS-422/485) communication adapters.

Free Modbus protocol with purchase of ProVu serial communications modules.


 

OUTPUTS

PD7000 dual-line process meter relay outputsRelay Outputs

The ProVu has up to four 3 A Form C relays (SPDT) with multiple power loss fail-safe options. Relays can be configured for proper protective action upon input loop break. Relay ON and OFF delay times are user adjustable. Up to eight front panel indicators show alarm and/or relay state. All relays can be configured for 0-100% deadband.


 

Relay Operation/Configuration

There are powerful relay functions that can be configured in the ProVu meter, including:

  • Automatic reset only (non-latching)
  • Automatic + manual reset at any time (non-latching)
  • Latching (manual reset only)
  • Latching with clear (manual reset only after alarm condition has cleared)
  • User selectable fail-safe operation
  • Relay action upon sensor break
  • Time delay (on and off), independent for each relay
  • Manual control mode
  • Interlock Relay Mode

Front panel button or digital input may be assigned to acknowledge relays programmed for manual reset.


 

Analog Output

The isolated analog output signal can be configured to represent the measured temperature (including average temperature), maximum or minimum temperature, any of the eight relay set points, manual control setting, or Modbus input. While the output is nominally 4-20 mA, the signal will accurately accommodate under- and over-ranges from 1 to 23 mA. A power supply (24 V @ 40 mA) is standard with the 4-20 mA output option.

Auto/Manual Control
 

Auto/Manual Control

Take control of any output with this feature. All relays can be forced ON or OFF, and the 4-20 mA output signal can be set to any value within its range. When the relays and 4-20 mA output are controlled manually, an LED labeled "M" is turned on and the associated Alarm LEDs (1-8) flash every 10 seconds indicating that the meter is in manual control mode.



ProVu Interlocking Relay

Interlock Relay(s)

This function allows a process to use one or more very low voltage input signals or simple switch contacts to control the state of one or more internal "interlock" relays. A violation (i.e. loss of input, open switch, or open circuit) forces one or more N/O interlock relay contacts to open. One input can be used in series with a number of interlock switches, or up to eight inputs can be required to force-on one (or more) internal interlock relays. Please see Application Note AN-1008 for more information.


Note: Requires PDA1044 Digital I/O module.


NEMA 4 & 4X FIELD ENCLOSURES

Thermoplastic and stainless steel NEMA 4X, and painted steel NEMA 4 enclosures for up to 10 ProVu meters are available. Please visit our Enclosure Selection Utility at www.predig.com/esu for an easy way to find the right enclosure.
Enclosure Selection Utility
Enter the Enclosure Selection Utility

 
PD6000 dual-line 6 digit process meter NEMA 4 and 4X field enclosure

CONNECTIONS


  • Form C (SPDT) relays
  • Isolated supply available even on 12/24 VDC input power models
  • Removable terminal blocks
  • 2 or 4 relays + isolated 4-20 mA output option
  • Universal 85-265 VAC or 12/24 VDC input power
  • Thermocouple or RTD inputs
  • M-Link for adding expansion modules
PD7000 Connections

MOUNTING DIMENSIONS

PD7000 dual-line 6 digit process meter mounting dimensions

 

Notes:
1. Panel cutout required: 1.772" x 3.622" (45mm x 92mm)
2. Panel thickness: 0.040 - 0.250" (1.0mm - 6.4mm)
3. Mounting brackets lock in place for easy mounting
4. Clearance: Allow 6" (152 mm) behind the panel.


 

SPECIFICATIONS

Except where noted all specifications apply to operation at +25°C.
 

General

Display: upper display: 0.60" (15 mm) high, lower display: 0.46" (12 mm) high. Both displays are 6-character (-99999 to 999999), red LEDs with leading zero blanking. Temperature value is four or five-digit F/C, based on configuration.
Resolution: 1° (up to four digits) or 0.1° (up to five digits)
Display Intensity: Eight intensity levels
Display Update Rate: 5/second (200 ms)
Front Panel: NEMA 4X, IP65
Programming Methods: Four front panel buttons, digital inputs, PC and MeterView Pro Software, Modbus registers, or cloning using Copy function.
Noise filter: Programmable from 2 to 199 (0 will disable filter)
Filter Bypass: Programmable from 0.1 to 99.9% of span
Recalibration: Calibrated at the factory. Recalibration is recommended at least every 12 months.
Max/Min Display: Max / min temperature readings are stored until reset by the user or until power to the meter is cycled.
Password: Three programmable passwords restrict modification of programmed settings. Pass 1: Allows use of function keys and digital inputs. Pass 2: Allows use of function keys, digital inputs and editing set/reset points. Pass 3: Restricts all programming, function keys, and digital inputs.
Non-Volatile Memory: All programmed settings are stored in nonvolatile memory for a minimum of ten years if power is lost.
Power Options: 85-265 VAC 50/60 Hz, 90-265 VDC 20 W max, or jumper selectable 12/24 VDC ±10%, 15 W max.
Fuse: Required external fuse: UL Recognized, 5 A max, slow blow; up to 6 meters may share one 5 A fuse.
Normal Mode Rejection: Greater than 65 dB at 50/60 Hz
Isolation: 4 kV input/output-to-power line. 500 V input-to-output
Environmental: Operating temperature range: -20 to 65°C. Storage temperature range: -40 to 85°C. Relative humidity: 0 to 90% non-condensing.
Connections: Removable screw terminal blocks accept 12 to 22 AWG wire, RJ45 for external relays, digital I/O, and serial communication adapters.
Enclosure: 1/8 DIN, high impact plastic, UL 94V-0, color: black
Mounting: 1/8 DIN panel cutout required: 3.622" x 1.772" (92 mm x 45 mm). Two panel mounting bracket assemblies are provided.
Tightening Torque: Screw terminal connectors: 5 lb-in (0.56 Nm)
Overall Dimensions: 4.68" x 2.45" x 5.64" (119 mm x 62 mm x 143 mm) (W x H x D)
Weight: 9.5 oz (269 g)
UL File Number: UL & c-UL Listed. E160849; 508 Industrial Control Equipment.
Warranty: 3 years parts & labor
 

Temperature Input

Inputs: Thermocouple J, K, T, E, R, S, B, N, C; RTD 100 Ω platinum (0.00385 & 0.00392 curves), 10 Ω copper, 120 Ω nickel, 1000 Ω platinum
Input Impedance: Greater than 100 k Ω
Offset Adjust: User programmable offset adjust ±50.0 degrees
Temperature Drift: ±2°C maximum from 0 to 65°C ambient temperature; ±4°C maximum from -20 to 0°C ambient temperature
Sensor Break: Display flashes "Open", relays can be programmed to go "On", "Off", or to "Ignore" (detected as an upscale condition).
Averaging: Up to 10 RTDs connected in parallel can be averaged.
Accuracy & Range: See table below.

Type      Range (°F)      Range (°C) Accuracy
J    -200 to 2000   -129 to 1093 ±1°C
K    -200 to 2400   -129 to 1316 ±1°C
T  -200 to 752 -129 to 400 ±1°C
E    -200 to 1800 -129 to 982 ±1°C
R       -50 to 3000      -46 to 1649 ±2°C
S       -50 to 3000      -46 to 1649 ±2°C
B      752 to 3300     400 to 1816 ±2°C
N    -100 to 2300      -73 to 1260 ±2°C
C        32 to 4100          0 to 2260 ±2°C
10 Ω  -328 to 500  -200 to 260 ±0.1°C
100 Ω    -328 to 1562  -200 to 850 ±0.4°C
120 Ω  -110 to 500    -79 to 260 ±0.1°C
1000 Ω  -328 to 900  -200 to 482 ±0.4°C

 

Relays

Rating: 2 or 4 SPDT (Form C) internal and/or 4 SPST (Form A) external; rated 3 A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP (approx. 50 watts) @ 125/250 VAC for inductive loads such as contactors, solenoids, etc.
Noise Suppression: Noise suppression is recommended for each relay contact switching inductive loads.
Deadband: 0-100% of span, user programmable
High or Low Alarm: User may program any alarm for high or low trip point. Unused alarm LEDs and relays may be disabled (turned off).
Relay Operation: Automatic (non-latching), latching (requires manual acknowledge), sampling (based on time), pump alternation control (2 to 8 relays), Off (disable unused relays and enable interlock feature, manual on/off control mode).
Time Delay: 0 to 999.9 seconds, on & off relay time delays. Programmable and independent for each relay.
Fail-Safe Operation: Programmable and independent for each relay.
Note: Relay coil is energized in non-alarm condition. In case of power failure, relay will go to alarm state.
Auto Initialization: When power is applied to the meter, relays will reflect the state of the input to the meter.
 

Isolated 4-20 mA Transmitter Output

Output Source: PV (temperature), max, min, set points 1-8, manual control setting, or Modbus input
Scaling Range: 1.000 to 23.000 mA for any display range
Calibration: Factory calibrated 4-20 mA output
Accuracy: ± 0.1% of span ± 0.004 mA
Temperature Drift: 0.4 µA/°C max from 0 to 65°C ambient, 0.8 µA/°C max from -40 to 0°C ambient
Note: Analog output drift is separate from input drift.
Isolated Transmitter Power Supply: Terminals I+ & R: 24 VDC ± 10% @ 40 mA maximum, may be used to power the 4-20 mA output or other devices. Present on both AC & DC powered units.
External Loop Power Supply: 35 VDC maximum
Output Loop Resistance:
Power supply Minimum Maximum
24 VDC 10 Ω 700 Ω
35 VDC (external) 100 Ω 1200 Ω

Serial Communications

Protocol: Modbus® RTU
Meter Address/Slave ID: 1 - 247
Baud Rate: 300 - 19,200 bps
Transmit Time Delay: Programmable between 0 and 199 ms or transmitter always on for RS-422 communication
Data: 8 bit (1 start bit, 1 or 2 stop bits)
Parity: Even, odd, or none with 1 or 2 stop bits
Byte-to-Byte Timeout: 0.01 - 2.54 seconds
Turn Around Delay: Less than 2 ms (fixed)
Note: Refer to the PD6000/PD7000 Modbus Register Tables for details, available in Documentation
 

Digital I/O Expansion Module

Channels: 4 digital inputs & 4 digital outputs per module
System: Up to 2 modules for a total of 8 inputs & 8 outputs
Digital Input Logic: High: 3 to 5 VDC Low: 0 to 1.25 VDC
Digital Output Logic: High: 3.1 to 3.3 VDC Low: 0 to 0.4 VDC
Source Current: 10 mA maximum
Sink Current: 1.5 mA minimum
+5 V Terminal: To be used as pull-up for digital inputs only.
 

4-Relay Expansion Module

Relays: Four Form A (SPST) rated 3 A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP (approx. 50 watts) @ 125/250 VAC for inductive loads.
 

ORDERING INFORMATION

Products

ProVu PD7000: Standard Display Models

Model Description  
PD7000-6R0        ProVu Dual-Line 6-Digit Temperature Meter; No Options Installed; Powered from 85-265 VAC         
PD7000-6R2        ProVu Dual-Line 6-Digit Temperature Meter; 2 Relays; Powered from 85-265 VAC         
PD7000-6R3        ProVu Dual-Line 6-Digit Temperature Meter; 4-20 mA Output; Powered from 85-265 VAC         
PD7000-6R4        ProVu Dual-Line 6-Digit Temperature Meter; 4 Relays; Powered from 85-265 VAC         
PD7000-6R5        ProVu Dual-Line 6-Digit Temperature Meter; 2 Relays + 4-20 mA Output; Powered from 85-265 VAC         
PD7000-6R7        ProVu Dual-Line 6-Digit Temperature Meter; 4 Relays + 4-20 mA Output; Powered from 85-265 VAC         
PD7000-7R0        ProVu Dual-Line 6-Digit Temperature Meter; No Options; Powered from 12-24 VDC         
PD7000-7R2        ProVu Dual-Line 6-Digit Temperature Meter; 2 Relays; Powered from 12-24 VDC         
PD7000-7R3        ProVu Dual-Line 6-Digit Temperature Meter; 4-20 mA Output; Powered from 12-24 VDC         
PD7000-7R4        ProVu Dual-Line 6-Digit Temperature Meter; 4 Relays; Powered from 12-24 VDC         
PD7000-7R5        ProVu Dual-Line 6-Digit Temperature Meter; 2 Relays + 4-20 mA Output; Powered from 12-24 VDC         
PD7000-7R7        ProVu Dual-Line 6-Digit Temperature Meter; 4 Relays + 4-20 mA Output; Powered from 12-24 VDC         

ProVu PD7000: SunBright Display Models

Model Description  
PD7000-6H0        ProVu SunBright Display Dual-Line 6-Digit Temperature Meter; No Options Installed; Powered from 85-265 VAC         
PD7000-6H2        ProVu SunBright Display Dual-Line 6-Digit Temperature Meter; 2 Relays; Powered from 85-265 VAC         
PD7000-6H3        ProVu SunBright Display Dual-Line 6-Digit Temperature Meter; 4-20 mA Output; Powered from 85-265 VAC         
PD7000-6H4        ProVu SunBright Display Dual-Line 6-Digit Temperature Meter; 4 Relays; Powered from 85-265 VAC         
PD7000-6H5        ProVu SunBright Display Dual-Line 6-Digit Temperature Meter; 2 Relays + 4-20 mA Output; Powered from 85-265 VAC         
PD7000-6H7        ProVu SunBright Display Dual-Line 6-Digit Temperature Meter; 4 Relays + 4-20 mA Output; Powered from 85-265 VAC         
PD7000-7H0        ProVu SunBright Display Dual-Line 6-Digit Temperature Meter; No Options; Powered from 12-24 VDC         
PD7000-7H2        ProVu SunBright Display Dual-Line 6-Digit Temperature Meter; 2 Relays; Powered from 12-24 VDC         
PD7000-7H3        ProVu SunBright Display Dual-Line 6-Digit Temperature Meter; 4-20 mA Output; Powered from 12-24 VDC         
PD7000-7H4        ProVu SunBright Display Dual-Line 6-Digit Temperature Meter; 4 Relays; Powered from 12-24 VDC         
PD7000-7H5        ProVu SunBright Display Dual-Line 6-Digit Temperature Meter; 2 Relays + 4-20 mA Output; Powered from 12-24 VDC         
PD7000-7H7        ProVu SunBright Display Dual-Line 6-Digit Temperature Meter; 4 Relays + 4-20 mA Output; Powered from 12-24 VDC         
 

Enclosures

PDA2300 Enclosure Family Enclosure Selection Utility
Model Description  
PDA2302        Economical Plastic NEMA 4X Enclosure for 2 Type A, B, C, or E Meters         
PDA2303        Economical Plastic NEMA 4X Enclosure for 3 Type A, B, C, or E Meters         
PDA2304        Economical Plastic NEMA 4X Enclosure for 4 Type A, B, C, or E Meters         
PDA2305        Economical Plastic NEMA 4X Enclosure for 5 Type A, B, C, or E Meters         
PDA2306        Economical Plastic NEMA 4X Enclosure for 6 Type A, B, C, or E Meters         
PDA2307        Economical Plastic NEMA 4X Enclosure for 7 Type A, B, C, or E Meters         
PDA2308        Economical Plastic NEMA 4X Enclosure for 8 Type A, B, C, or E Meters         
PDA2309        Economical Plastic NEMA 4X Enclosure for 9 Type A, B, C, or E Meters         
PDA2310        Economical Plastic NEMA 4X Enclosure for 10 Type A, B, C, or E Meters         
PDA2312        Economical Plastic NEMA 4X Enclosure for 2 Type A, B, C, or E Meters         
PDA2322        Economical Plastic NEMA 4X Enclosure for 1 Type D + 1 Type C Meter         
PDA2407        Plastic NEMA 4X Enclosure for 1 Meter (Any Type)         
PDA2411        Plastic NEMA 4X Enclosure for 2 Meter (Any Type)         
PDA2414        Plastic NEMA 4X Enclosure for 1 Type D + 1 Type A, B, C or E Meter         
PDA2504        Plastic NEMA 4X Enclosure for 4 Type A, B, C, or E Meters         
PDA2505        Plastic NEMA 4X Enclosure for 5 Type A, B, C, or E Meters         
PDA2506        Plastic NEMA 4X Enclosure for 6 Type A, B, C, or E Meters         
PDA2507        Plastic NEMA 4X Enclosure for 7 Type A, B, C, or E Meters         
PDA2508        Plastic NEMA 4X Enclosure for 8 Type A, B, C, or E Meters         
PDA2509        Plastic NEMA 4X Enclosure for 9 Type A, B, C, or E Meters         
PDA2510        Plastic NEMA 4X Enclosure for 10 Type A, B, C, or E Meters         
PDA2512        Plastic NEMA 4X Enclosure for 2 Type A, B, C, or E Meters         
PDA2522        Plastic NEMA 4X Enclosure for 1 Type D + 1 Type C Meter         
PDA2604        Stainless Steel NEMA 4X Enclosure for 4 Type A,B, C or E Meters         
PDA2605        Stainless Steel NEMA 4X Enclosure for 5 Type A,B, C or E Meters         
PDA2606        Stainless Steel NEMA 4X Enclosure for 6 Type A,B, C or E Meters         
PDA2622        Stainless Steel NEMA 4X Enclosure for 1 Type D + 1 Type C Meter         
PDA2704        Steel NEMA 4 Enclosure for 4 Type A, B, C, or E Meters         
PDA2705        Steel NEMA 4 Enclosure for 4 Type A, B, C or E Meters         
PDA2706        Steel NEMA 4 Enclosure for 5 Type A, B, C or E Meters         
PDA2722        Steel NEMA 4X Enclosure for 1 Type D + 1 Type C Meter         
PDA2811        Low-Cost Plastic NEMA 4X Enclosure for 1 Meter (Type A, B, C or E)         
PDA2812        Low-Cost Plastic NEMA 4X Enclosure for 2 Meters (Any type)         
PDA2821        Low-Cost Plastic NEMA 4X Enclosure for 1 Type D Meter + 1 Type A, B, C or E Meter         
  

Accessories

Model Description  
 PDA1002        ProVu DIN Rail Mounting Kit for Two Modules         
 PDA1004        ProVu 4 Relays Expansion Module         
 PDA1044        ProVu 4 Digital Inputs & 4 Outputs Module         
 PDA1200        ProVu Meter Copy Cable, 3' (0.9 m)         
 PDA1232        ProVu RS-232 Serial Adapter         
 PDA1485        ProVu RS-422/485 Serial Adapter         
 PDA7485-I        RS-232 to RS-422/485 Isolated Converter         
 PDA7485-N        RS-232 to RS-422/485 Non-Isolated Converter         
 PDA8232-N        USB to RS-232 Converter         
 PDA8485-I        USB to RS-422/485 Isolated Converter         
 PDA8485-N        USB to RS-422/485 Non-Isolated Converter         
 PDA9485-01        Ethernet Serial Server         
 PDX6901        Suppressor (snubber): 0.01µF/470Ω,